TRANSFORMERS
SWITCHGEAR / VACUUM CIRCUIT BREAKERS
CARGO TROLLEY
CAPACITOR BANKS
MEASUREMENT DEVICES
PF REGULATORS
CAPACITORS
CONTACTOR
MOULDED CASE CIRCUIT BREAKERS
USED PRODUCTS
 


VMX
Indoor Vacuum Circuit Breaker

The vertically isolated vacuum circuit breakers was introduced in 1985, in the well-established range of distgribution switchgear of AREVA T&D. This principle combined the advantages of British and International operating practices with modern vacuum technology.

The type VMX design utilises time tested mechanism and AREVA make contemporary technology interrupters. VMX panels have logged more operation hours in the field than any other design in the country, having a presence of three decades. The moving portion comprises a truck-mounted circuit breaker with operating mechanism and incorporates vacuum interrupters manufactured in-house by AREVA T&D.

VMX range is the simple, robust & time tested equipment which is tested for internal arc. With simple operating mechanism and linkages VMX range is the most reliable switchgear. It uses breaker transfer principle for earthing which makes it safe. The trefoil arrangement allows lowest possible width (540mm). The in-house vacuum interrupter guarantees high life. It is a Metal Clad switchgear, fully insulated, dead front type with front door.

Approximate Weight (kg)
Type Current rating Moving portion Fixed portion
Standard VMX 630 A 260 585
Standard VMX 1250 A 310 711

Dimension (mm)
Type Current rating Moving portion Fixed portion
Standard VMX* 606 1867 2000
Low width VMX# 540 1360 2000

Technical Specification
Technical Specification
Rated voltage 12kV
Rated continuous current upto 1250 A
Rated frequency 50 Hz
Rated interrupting current upto 26.3 kA (rms)
Rated making current 65.5 kA (p)
Rated short time (3 sec.) current 26.3 kA (rms)
Operating duty O-0.3 sec-CO-3 min - CO (rapid auto reclosing duty on request)
Applicable standard IEC 60056 IEC 56 (1987) / IS 13118 (1991)
Power frequency withstand voltage 28/35 kV (rms)
Impulse withstand voltage 75k(p)
Busbar rating upto 2000 A


 

AIR INSULATED
METALCLAD SINGLE BUSBAR SWITCHGEAR
8BK88
Type 8BK88 metal-clad switchgear is horizontal isolation and horizontal drawout type (site extensible) in both directions for system voltage up to 12kV. The switchgear is designed for single busbar system and is fully compartmentalised. The design incorporates a set of interlocks for safe operation of the switchgear.

1.1 Application

The switchgear is suitable for use as a distribution unit and a switching load.
The switchgear:
  • Is type tested and is supplied ready assembled.
    Incorporated with drawable vacuum circuit breaker or vacuum contactor.
  • Is available for a rated voltage up to 12kV.
  • Is free of standing type.
  • Type tested according to the following standards:
    IEC 298-1990/1S 2729-1988
1.2 Design features
1.2.1. Switchgear layout

Metal partitions subdivide each panel into
  • Circuit breaker compartment (1, Fig.2)
  • Busbar compartment (2, Fig.2)
  • Cable and CT compartment (3, Fig.2)
  • Low voltage compartment (4, Fig.2)

Each individual compartment is a separate housing, which is assembled separately and bolted, together to form a panel.
The outside covers are bolted to the frame and the doors are hinged.


EPE - 10F / 10D
12KV METALCLAD SWITCHGEAR

Switchgear Model  
EPE 10F
Single Bus
EPE10D
Double Bus
Rated voltage
kV
12
Power frequency withstand voltage
kV/ 1min
28
Lightning impulse withstand voltaage
kV, 1.2/50 µs
75
Rated frequency
Hz
50
Short time withstand current
kA / 3s
25
Peak withstand current
kA
63
Rated normal current in busbar
A
800/1250/2000
 
Stand degree of protection (1)
  • Enclosure
3X
  • Compartment
2X
 
Dimension
Width
mm
600
700
Depth
mm
1850
1950
Height
mm
2150
2400

 